150 6 6 square feet of total net free area 3.
Eave vent area to floor square ft ratio.
The irc adds that the nfva ratio can also be reduced to 1 300 if 50 to 80 of the required ventilation is located in the upper portion of the attic or cathedral ceiling and the rest is located at the eaves with the upper vents at least 3 feet above the lower.
40 x 25 1 000 square feet of attic area 2.
For square or rectangular vents muliply the length times width of the vent space in inches then divide by 144 to convert into sq.
Once attic square footage is known divide by 150 for the 1 150 ratio.
In divided by 144 equals an area of 0 5 sq.
A 6 x 12 vent would equal 72 sq.
1 500 square feet 300 5 square feet.
Determine the total net free area required.
That determines the total amount of net free area needed to properly ventilate the attic.
1 square foot of nfva per 300 square feet of attic floor if a vapor barrier is installed on the ceiling below.
L x w in inches 144 area of vent in sq.
This ratio is required for modern insulated homes.
Remember the minimum area requirement when using a continuous system is a ratio of 1 300.
Ok so now we know the square footage of the attic area to be ventilated.
Now let s figure out how much ventilation space we need.
So in our example we will divide the 1 500 square feet by 300.
30 feet x 50 feet 1 500 square feet.
Divide the square footage by 150 to calculate the area of ventilation needed since you need 1 square foot of vent space for each 150 square feet of attic space.
These methods dictate that one 1 square foot of ventilation is provided for every 150 or 300 square feet of attic floor space.